Skip to content

TechChannels Network:      Whitepaper Library      Webinars         Virtual Events      Research & Reports

×
Cybersecurity

Europe’s Fridge Hacks Expose a Weak Point in Cold-Chain Security

At a London produce wholesaler, someone remotely changed the defrost settings on several refrigeration units, instructing them to run for more than four hours at 150°C. Staff at Langridge Organic caught the changes and disconnected the controllers from the internet before stock was damaged. That figure was a programmed setting, not evidence that the cold rooms actually reached 150°C. Just like that, an outsider could alter their operating instructions (The Guardian, 2026).

Similar disruptions have occurred in supermarkets in seven EU countries following the attacks in France in October. UK meat suppliers have also had units compromised, though the NCSC has stated the impact across the UK was very limited, and no meat was lost in those incidents. The attackers' ability to interfere with refrigeration is a vulnerability that goes far beyond supermarkets.

Commercial refrigeration is increasingly run via supervisory controllers that allow technicians to adjust temperatures, schedule defrost cycles, and monitor alarms remotely. The Danfoss AK-SM and AK-SC and the Copeland/Dixell XWEB are examples of such systems which sit above the individual cooling units. The management interface can issue commands to the field controllers, which in turn control the compressors, fans, and defrost heaters (Claroty, 2026). The commands are typically issued via an industrial protocol such as Modbus. Remote access enables maintenance to be carried out much more efficiently, particularly for large supermarket chains. It also means that an exposed management interface can be exploited by an intruder to directly influence a physical process. A defrost cycle could be altered to warm the stock; alarms could be disabled to delay their detection. This attacks the system's operational integrity and could have serious implications for food safety, waste, and business continuity.

France's CERT-FR confirmed multiple compromises relating to those controller families in an October alert. They highlighted the danger of exposing management interfaces directly to the internet and advised operators to remove public access, review defrost configurations, and restore connectivity only via protected networks (CERT-FR, 2026).

The weaknesses were documented before the attacks

Security researchers have already shown how serious controller flaws can be. In August, Team82 of Claroty reported 23 flaws in Copeland XWEB Pro, 21 of which were high severity. One of the authentication bypass issues (CVE-2026-21718) has a maximum CVSS score of 10.0 and could allow code execution without valid credentials. Claroty also found authentication bypass and command injection flaws in Danfoss's AK-SM 800A platform (Danfoss, 2026).

Copeland released firmware version 1.13 to address the various XWEB Pro vulnerabilities that had been identified and had clearly advised customers not to expose their controllers to the public internet (Copeland, 2026). The exact exploit paths that were used in the recent incidents haven't been made public. The existence of documented vulnerabilities doesn't necessarily mean that those were the paths used to compromise every one of the victims. Besides, the attackers' identity is still unknown. Lupovis reported 256 attempts from 91 sources against decoy Danfoss controllers over a 10-day period, many of the attempts using well-known factory credentials. Some overlap with infrastructure previously linked to Russian-linked activity, but that's not enough to attribute the refrigeration attacks to any one group.

The immediate priority is to identify any exposed supervisory controllers, remove their direct internet access, ensure they run supported firmware, and change their default credentials. Remote maintenance should continue via authenticated, restricted connections with independent temperature alarms and a procedure in place to run the cooling system if the connection is lost. The retailer must also know which contractor is responsible for each controller and who is responsible for the security updates to that controller.

NCSC chief executive Richard Horne warned (NCSC, 2026) about long-neglected operational technology as a growing source of exposure, noting “We have installed technology then failed to invest in it throughout its lifecycle.”

Share on

More News